EMI/RFI Shield Enclosure for EEG Laboratory at a University

On 9 February 2002, VitaTech Engineering was contracted by a university to design, install, test and certify a AC ELF EMI/RFI magnetic shield. Between May 10th and May 13th 2002, VitaTech installed a 9' x 12' x 8'(height) shield composed of conductive seam welded aluminum plates and extruded aluminum I-Beams. Additionally, an RF sealed door and filtered penetrations for HVAC and signal cables were installed to complete the design. Low (0.1-9.99 mG) AC ELF magnetic emissions emanated into room #240 from 60 Hz sources inside the room and from the electrical closet located across the hallway. In addition, the high frequency noise from multiple sources needed to be attenuated for the newly proposed EEG laboratory.

Site Survey

Before Shield
Data Collected at Floor Level

Before Shield
Data Collected at 1 Meter Level

Slideshow

 

BEFORE DATA:

Inside Shielded Area
5 Hz - 100 KHz
Electric Field
Er Range @ 1-m
Inside Shielded Area
100 KHz -3 GHz
Electric Field
Er Range @ 1-m
Inside Shielded Area
60 Hz
Magnetic Field
Br Range @ 1-m
Min: 0.158 V/m Min: 0.000 V/m Min: 0.1 mG
Max: 0.825 V/m Max: 3.200 V/m Max: 2.64 mG
Mean: 0.274 V/m Mean: 1.112 V/m Mean: 0.46 mG

 

AFTER DATA:

Inside Shielded Area
5 Hz - 100 KHz
Electric Field
Er Range @ 1-m
Inside Shielded Area
100 KHz -3 GHz
Electric Field
Er Range @ 1-m
Inside Shielded Area
60 Hz
Magnetic Field
Br Range @ 1-m
Min: 0.000 V/m Min: 0.000 V/m Min: 0.0 mG
Max: 0.000 V/m Max: 0.000 V/m Max: 0.0 mG
Mean: 0.000 V/m Mean: 0.000 V/m Mean: 0.0 mG