Electric Charge, Current & Voltage
Electric charge, whether negative electrons or positive
protons, is measured in units called coulombs (C), where one
coulomb has the charge of 6 x 10E+18 electrons or protons. Electric
charges exist both in free space (t hunder storms) and on conductive
materials (wires, metal, glass, rugs, water, etc.). When an electric
charge is in motion it is called current, which is measured
in amperes (A). One ampere is equal to one coulomb of e
lectric charge per second past a defined reference point. The electric
potential between two points, defined as voltage (V), is the
work measured in joules per coulomb (or voltage)
necessary to move a unit electri c charge between the two points.
Electric & Magnetic Fields
Electric fields E, a vector quantity measured
in volts per meter (V/m), are created by electric charges in
free space and on conductive objects. Electric fields emanate
out and down toward the ground diminishin g in magnitude (field strength)
at a linear 1/r rate from line sources (unshielded transmission
lines, etc.) and at a nonlinear 1/r² distance rate from point
sources (appliances). Near extra-high voltage (EHV) transmission lines,
defined as between 230-765 kilovolts (kV), one can hear the corona
(crackle) produced by ionizing air molecules and sense the presence (tingle)
of electric fields on the hair and skin. Under the midspan of a 230 kV
and 500 kV transmission line, the electri c field strength is
2 kV/m and 7 kV/m, respectively, three feet above the ground; more than
enough to illuminate a hand-held fluorescent tube. Fortunately, grounded
conductive objects including trees, bushes, buildings, and metal conduits
easily atten uate (reduce) or completely shield electric fields.
Therefore, properly grounded metal conduits and equipment cases do not
emanate electric fields.
Magnetic fields H, a vector quantity measured
as amperes per meter (A/m) in the MKS system and oersted (Oe)
in the CGS system, are generated when electric charges are moving
in free space and within conductors. High current sources such as lightning,
transmission and distribution lines, transformers, network protectors,
secondary feeders, switchgears, distribution busways, electrical panels,
motors, and electric heaters produce very high magnetic fiel ds.
Unfortunately, magnetic fields are extremely difficult to shield
and easily permeate (penetrate) nearly all materials including people,
trees, buildings, equipment, and most metals except special ferromagnetic
and highly conductive (copper and aluminum) materials. Normally, people
are not able to sense the presence of very high 10-1,000 mG magnetic
fields; however, extremely high levels exceeding 100 Gauss (100,000
mG) will cause a temporary visual flickering sensation called magn
etophosphenes which disappears when the field is removed.
Table of Contents
Magnetic Flux Density & Handy
Conversion Factors
When an emanating magnetic field H permeates
through a cross-sectional area of a medium (vacuum, free space or material),
it converts to magnetic flux density B according to the
following formula:
- Bmagnetic flux density = µHmagnetic field where µ is
the permeability of the medium
The permeability of a vacuum designated as µo and
free space (air) are nearly identical: 4 x 10E-7 henry per meter (H/m)
in MKS units and 1-gauss/oersted in CGS units. Magnetic flux
density B is de fined in MKS units as tesla (T) and
in CGS units as gauss (G). It should be noted that in the United
States CGS units oersted (Oe), gauss (G), and milligauss (mG)
are the normal convention in power engineering and electr omagnetics
rather than the MKS units, except in scientific journals. Also, when
working in free space both gauss (G) and oersted (Oe) are
equal in magnitude as shown:
- Bgauss = µoHoersted where µo
= 1-gauss/oersted.
For example, a 0.020 oersted magnetic field H in
free space is equal to a magnetic flux density B of .020 gauss (20
mG). Although not technically accurate, the terms magnetic field H and magnet
ic flux density B usually appear synonymous in the engineering
literature. Magnetic flux density B is measured with a
gaussmeter in milligauss (mG) and easily converted to magnetic
field H in either CGS and MK S units with the handy conversion
factors listed below:
ELF
EMF, 60-Hz Wavelength, DC & AC Fields Electric power generated in North America is 60-Hz alternating
current (AC). This means both the voltage and current are
sinusoidally varying (change polarity twice in each cycle or 120 times
every second). The 60-Hz AC line frequency has a monstrous wavelength
of 3,100 miles (5,000 km) calculated between cycles using:
Cspeed-of-light = ( wavelength)(frequency). Alternating current (AC) electric and magnetic fields fluctuate in
space as the sinusoidally varying voltage and current change polarity,
whereas DC fields (like the earth's geomagnetic field) remain
statically polarized based upon the di rection of the current flow (remember
the Right Hand Rule). Incidentally, the geomagnetic (static) field
is typically 670 mG at the magnetic poles, 500 mG around the middle latitudes,
and 330 mG on the equator. Furthermore, when the distance from a sinusoidally
varying source such as 60-Hz AC power is small with respect to the wavelength
(known as the near field), the electric and magnetic fields are not coupled
and considered separate physical entities. That is why 60-Hz electric
fields can be gro unded to zero inside a metal conduit; however, the
unperturbed magnetic fields will still emanate through the conduit. The
opposite is true for radio frequency sources that have significantly
shorter wavelengths and radiate coupled electric and magnetic f ields
into free space several wavelengths from the antenna (known as the far
field).
Table of Contents
Electrostatic & Electromagnetic
Induction
Electrostatic induction occurs when alternating 60-Hz electric
fields couple with conductive animate (humans) and inanimate objects,
thereby inducing currents and voltages within the objects. The actual
current consists of minute movements o f charged particles: electrons
in metallic conductors and ionic conduction in body tissues and fluids.
The voltages and currents induced directly into humans are of concern
if they are high enough to cause direct biological, physiological, and
psychologic al effects.
If the conductive object is grounded, the induced current
that travels through the object to the ground is called the short-circuit current
(units in amperes). Generally, in humans and animals the short-circuit
current flows from head to feet (c alled body currents) and can be approximated
with the following formula: Ishort-circuit (microamps) = 5.4(h²height(meters))(EkV/m).
Examples of measured short-circuit c urrents in 2 kV/m and 7 kV/m
electric fields similar to those under 230 kV and 500 kV overhead transmission
line are presented below in microamps (µA):
Within elevated electric fields, when a grounded
person touches an isolated (ungrounded) conductive object, a perceptible
current (tingling sensation) or shock may occur. This phenomena also
happens when the person is insulated and the conductiv e object is grounded.
There are three basic classifications for shocks: perception and secondary
shocks (which are annoying but not harmful) and primary shocks (which
are very dangerous and potentially lethal). A safe perception shock (tingling
response) for most men and women is 1.0 mA and 0.65 mA, respectively.
Secondary shocks invoke involuntary muscle responses (shaking) that are
very annoying and possibly painful. However, primary shocks begin at
the let-go current where 99.5 % of all subjects can still voluntarily let-go of
an energized conductor: 9.0 mA for men and 6.0 mA for women. Unfortunately,
beyond the let-go current threshold, a victim's heart may be shocked
into ventricular fibrillation resulting in imminent death if no t medically
treated (defibrillated) within 4-6 minutes. Near transmission lines,
the National Electrical Safety Code (N.E.S.C.) specifies 5 mA as the
maximum allowable short-circuit current from vehicles, trucks,
and equipment. And the American Nat ional Standard Institute (ANSI) allows
up to 0.5 mA leakage current from portable household appliances and 0.75
mA for fixed appliances.
Electromagnetic induction occurs when alternating
60-Hz magnetic fields couple with animate (humans) and inanimate conductive
objects (wires, metal beams, HVAC ducts, etc.), thereby inducing circulating
currents and voltages. Magnetically induce d body currents in human tissues
flow primarily in peripheral loops (called eddy currents) perpendicular
to the field; however, current at the center is generally near zero.
Magnetic fields from transmission lines will normally induce voltages
at the open ends of long, partially grounded, parallel conductors (fences,
wires, and exposed pipes). So, dangerous and potentially lethal shocks
from electromagnetic induction are also a serious problem.
Unfortunately, electromagnetic induction generates
circulating tissue currents in humans near transformers, network protectors,
secondary feeders, switchgears, distribution busways, and electrical
panels. In calculating the current den sity in human tissues
due to electromagnetic induction, the conductivity of mammalian
tissue is assumed to be uniform: conductivity = 0.1 S/m(siemens/meter).
Assuming the human body is within a conducting sphere, the induced voltage E
i in volts/meter (V/m) at a defined radius r in meters representing
a waist of .145 m (36 in.) is defined as:
Ei = (1 x 10E-7)(PI)(r)(frequency)(BmG).
The current density Jbody in microamps/meter² (µA/m²)
for human body tissues around the waist can be calculated by using:
Jbody = (conductivity)(Ei).
Below is a list of 60-Hz calculated electromagnetically
induced voltages Ei and current densities Jbody around
a typical waist exposed to various magnetic flux density BmG levels
(also equivalent s hort-circuit currents induced within humans from Efield
electrostatic induction in italics):
Table of Contents
Loop Magnetic Field Sources
The first basic magnetic field source
is a single loop (actually multiple) of current that approximates a magnetic
dipole such as AC motors, transformers, computers, power supplies,
analog clocks, electric stoves, and microwave ovens. Using the Right
Hand Rule, a magnetic dipole has a vector dipole moment m (direction
of thumb) in amps/meter² with a magnitude equal to the product of
the loop current Iamps(fingers curl around the loop) and the enclosed
loo p area Asquare meters expressed as:
m = (Iamps)(Asquare meters). Magnetic dipoles produce complex magnetic
fields that diminish at a 1/r³ distance rate in meters from the
source according to the formula:
BmG = 2(Iamps)(Asq.meters)/r³meters.
For example, the magnetic fields from a distribution transformer
can be calculated by using the secondary per phase current Iamps and
a scaling factor of 1-mG·m³/A for Asq.meters in
the a bove formula.
Table of Contents
Single Conductor Magnetic
Field Sources
The second basic magnetic field source is a straight, single
conductor of current that is represented by the formula:
It also applies to ground, plumbing and net currents plus
electrically powered subway, rail, and trolley-bus systems with either
an overhead electrified cable (pantograph) or third-rail. The magnetic
fields from a single conductor are circular emanating out from
the center and impossible to magnetically shield (with a conduit
or enclosure) using any material including highly permeable mumetals
(flux-entrapment) or highly conductive copper and aluminum (eddy-current)
materials ( see EMF Fundamentals - Rigid Magnetic Shielding).
Fortunately, passive and active magnetic field cancellation technology
will mitigate single conductor and net, ground, and plumbing
current magnetic fields.
Table of Contents
Dual Conductor Magnetic Field
Sources
The magnetic field for an opposing current pair of
dual conductors (single phase pair, electrical appliance cord, knob-and-tube
wiring, etc.) separated by a small distance dmeter between the
conductors relative to the distance from the pair rmeters diminishes
at a nonlinear 1/r²distance rate according to the formula:
BmG = 2(Iamps)(dmeters)/r²meters.
This is the famous inverse square law that also
applies to radiating radio frequency (RF) EMF, electric fields, light,
sound, and of course gravity. Basically, by doubling the distance rmeter
for a fixed spacing dmeter and current load Iamps, the
magnetic flux density reduces by a factor of four (4). For example, the
magnetic flux density BmG levels at 1, 2 & 4-inches (r = .025
m, .05 m & .1 m) from a typical electri cal cord (spacing d=.001
m) with a 10 amp load are 32 mG, 8 mG, and 2 mG, respectively.
Table of Contents
Three-Phase Magnetic Field
Sources
Electric power around the United States is generated
and distributed via three-phase AC transmission, distribution, and service
feeder lines to commercial, institutional, and industrial buildings.
Each of the three balanced phase voltages and curre nts are ideally represented
as phasers (magnitude and angle) 120 degrees apart. The magnetic field
for balanced three-phase circuits of three horizontally or vertically
arrayed conductors separated by equal distances dmeter diminishes at
a nonlinea r 1/r²distance rate according to:
BmG = 3.46(Iamps)(dmeters)/r²meters.
However, if the three-phase circuit is unbalanced and/or
there are significant net, ground, and plumbing currents on the
service feeder neutral (see next section for more details), then the
dominant magnetic field becomes:
BmG = 2(Iamps)/rmeter, where Iamps
is the sum of the net, ground, and plumbing currents. Finally,
magnetic fields produced by three phase lines are generally elliptically
polarized. This means the magnetic field can be represented by a rotating
vector that traces an el lipse for every cycle of the conductor currents.
Table of Contents
Ground, Plumbing & Net
Currents
Ground currents are a collective term for any errant electrical
currents measured in amperes (A) that result from the natural
grounding process to earth including currents on conduits, ground wires,
ground rods, building steel, metal HVAC ducts, and metal water pipes
(also known as plumbing currents). These ground currents normally
generate magnetic fields that emanate out from a grounding conductor
(ground wire, water pipe, metal HVAC duct, etc.) at a diminishing linear 1/rdistance rate
according to the formula:
Both ground currents and plumbing currents can
be easily calculated by recording the magnetic flux density at a measured
distance rfeet from the source:
However, it is much easier to use a clamp-on amp meter around
a grounding conductor or water pipe (if practical) for an accurate measurement.
Net currents, also known as unbalanced or zero-sequence
currents, are the vector sum of all the phase (conductor) currents. In
perfectly balanced, single-circuit, three-phase transmission and distribution
lines, the net current is zero wh en all three phase currents
are equal. Theoretically, if a clamp-on amp meter could be safely placed
around the three phase conductors it would measure zero amps -- indicating
no net current. However, if phases A and B were 1000 amps and phase C
1500 amps , there would be a measurable net current. This net
current produces a magnetic field that also diminishes at a linear 1/rdistance rate
like a ground or plumbing current according to:
For example, a 500 amp net, ground or plumbing current produces
a 1,000 mG field at 1 meter (3.3 ft.), 500 mG at 2 meters (6.6 ft.),
250 mG at 4 meters (13.2 ft.), 200 mG at 5 meters (16.5 ft.),100 mG at
10 meters (33 ft.), and finally a 3 m G at 333.3 meters (1094 ft.).
In commercial buildings, neutral net currents are
very problematic in four-wire three-phase wye service feeders (480V/277V
and 208V/120V). Ideally, when the three phases are unbalanced and there
are absolutely no neutral return currents f rom harmonic and transient
sources (reactive loads such as motors, computers, dimmers, heavy machinery,
etc.) and/or errant ground/plumbing currents, the unbalanced return
neutral current effectively cancels out the unbalanced phase current
resulti ng in zero net current: if and only if the four conductors
are bundled close together within the same conduit or busway. Typically,
there are complex harmonic and transient components on the return neutral
that generate noisy net currents . Frequently, externally produced
ground and plumbing currents from nearby electrical sources leak into
the return neutral via the neutral-ground bond in the switchgear and
migrate back to the multiground neutral (MGN) system. The cumulative
magnetic field that emanates from neutral net, ground, and plumbing
currents on service feeders presents a very serious EMI threat to
nearby sensitive electronic equipment and occupants.
Table of Contents
Video Display Terminals (VDTs)
Since 1990 most video display terminal (VDT) manufacturers
have voluntarily complied with the Swedish MPR2 and recent IEEE P1140
electric and magnetic field VDT emission standards. Levels are measured
50 cm (20 inches) from the monitor for two spec ific frequency bands
identified as ELF Band 1 (5 Hz - 2 kHz) and VLF Band 2 (2 kHz
- 400 kHz). To check electric fields a dual band probe is placed
at the screen center. Electric fields should measure less than 25
V/m (ELF Band 1) and 2.5 V/m (VLF Band 2). The monitor is
placed on a turn table (lazy susan) and rotated 360 degrees in 22.5 degree
increments when measuring magnetic fields with a dual band probe. Magnetic
fields should measure less than 2.5 mG (ELF Band 1) a nd 0.25
mG (VLF Band 2) throughout the full rotation at three fixed heights:
center screen and ±0.3 m (12 inches). Each year PC Magazine publishes
a list of monitors that comply with MPR2 and IEEE P1140 standards. It
should be noted that col or monitors purchased before 1990 generally
do not comply with the MPR2 standards.
Table of Contents
Magnetic Field Mitigation
There are two basic 60-Hz magnetic field mitigation (reduction)
methods: passive and active. Passive magnetic field mitigation includes
rigid magnetic shielding with ferromagnetic and highly conductive
materials, and the use of passive shield wires installed near
transmission lines that generate opposing cancellation fields from electromagnetic
induction (beyond the scope of this paper). Active magnetic field mitigation
uses electronic feedback to sense a varying 60-Hz magnetic field, then
generates a proportionally opposing (nulling) cancellation field within
a defined area (room or building) surrounded by cancellation coils. Ideally,
when the two opposing 180-degree out- of-phase magnetic fields of equal
magnitu de intersect, the resultant magnetic field is completely cancelled
(nullified). This technology has been successfully applied in both residential
and commercial environments to mitigate magnetic fields from overhead
transmission and distribution lines, an d underground residential distribution
(URD) lines.
Rigid Magnetic Shielding
Rigid magnetic shielding is divided into two
fundamental types based upon the magnetic properties of the materials: flux-entrapment
shields and lossy shields. A flux-entrapment shield is constructed
with highly permeable (µ), speciall y annealed ferromagnetic mumetal
alloy composed of 80% nickel and 20% iron (Hipernom Alloy, CO-NETIC AA,
Amumetal, AD-MU-80)
which either surrounds (cylinder or rectangular box) or separates ("U" shaped
or flat-plate) the victims from the magnetic source. Ideally, magnetic flux
lines incident upon the flux entrapment shield prefer to enter the
highly permeable (µ) material traveling inside the material via the
path of least magnetic reluctance-R, rather than passing into the protected (shiel
ded) space. The relative permeability (µr) of mumetal ranges between
350,000-500,000 depending on the composition and annealing process. Unfortunately,
mumetal sheets are extremely expensive: a single fully annealed 30 x 120
inch sheet (0.04-inches thick) costs around $1,250 (prices are very volatile
due
to fluctuation in nickel costs). Lossy shielding depends on the eddy-current losses
that occur within highly conductive materials (copper and aluminum),
and low permeable (µ) materials that are also conductive such as
iron, steel, and silicon-iron. When a conductive mate rial is subjected
to a time-varying (60-Hz) magnetic field, currents are induced within
the material that flow in closed circular paths -- perpendicular to the
inducing field. According to Lenz's Law, these eddy-currents oppose
changes in th e inducing field, so the magnetic fields produced by the
circulating eddy-currents attempt to cancel the larger external
fields near the conductive surface, thereby generating a shielding effect.
It is often very effective and extremely expensive t o shield with multiple
layers composed of low permeable/conductive materials (silicon-iron sheets
or 1010 annealed steel plates), highly conductive aluminum/copper plates,
and highly permeable mumetal sheets.
Shielding factor (SF) is the ratio between the unperturbed
magnetic field Bo and the shielded magnetic field Bi as
expressed in:
SF = Bi/Bo or decibels SFdB = 20log10(Bi/Bo).
The final shielding design depends on the following critical
factors: maximum predicted worst-case 60-Hz magnetic field intensity
(magnitude and polarization) and the earth's geomagnetic (DC static)
field at that location; shield geometry an d volumetric area; type of
materials and properties -- conductivity, permeability (µ), induction
and saturation which are a function of material thickness; number of
shield layers; and, the spacing between sheet materials and layers.
Small, fully-enclosed shields for video display terminals,
electronic equipment, and electrical feeders follow simple formulas that
guide the design engineer through the process to a functional, but not
necessarily optimal, design. After assembling a p rototype, the design
engineer measures the shielding factor (SF) and modifies the design
(adds materials, additional layers, anneals bends, etc.) to achieve the
maximum shielding requirements. This is a very iterative design process,
from concept t o final product. Unfortunately, magnetic shielding is
more of an art than a science, especially when shielding very large areas
and rooms from multiple, high-level, magnetic field sources. At
this time there are no reliable design formulas or EMF si mulation programs
that offer design engineers practical guidelines for shielding large
exposed areas from multiple, high- level, magnetic field sources.
To Shield or Not To Shield The Source?
It is usually not desirable, especially if office space
is limited, to evacuate an entire room or several rooms exposed to very
high magnetic field
levels. So, when space is at a premium the only other alternative is magnetic
shielding. To shiel d or not to shield the source? That is the question!
Generally, when physically practical, source shielding is the most effective
and least expensive alternative. However, if there are multiple magnetic
field sources (i.e., parallel transformer vaults , network protectors,
secondary feeders, etc.), it may not be economically feasible to separately
shield
each source. In that case, shielding the room, and consequently the victims,
is the preferred solution. Call a professional 60-Hz magnetic shie lding
company for a detailed magnetic field survey, site evaluation, and estimate.
Magnetic shielding is expensive, so don't be astounded by the quote to
magnetically shield an entire 50' x 40' room to 10 mG (SFdB of -34 dB to
-40 dB), measured
one-meter off the floor from 500-1,000 mG levels emanating from multiple
transformer vaults, network protectors, secondary feeders, and switchgears located
under or above the room. Finally, request a written 10 mG or
5 mG and less performance guarantee over 95% of the shielded room - only
VitaTech Engineering, LLC. can achieve this demanding performance requirement
using state-of-the-art shielding materials.
Magnetic Shielding Information
Several years ago the Electric Power Research Institute
(EPRI) published a two volume set Handbook of Shielding Principles
for Power System Magnetic Fields, April 1994, EPRI TR-103630-V1 & V2
for a mere $50,000, a new price based on deregulation of the power utility
industry. These
two huge volumes provide an encyclopedic treatise on 60-Hz magnetic field
mitigation; however, there are very few practical shielding design equations
and useful examples. So, if you are a design engineer, first experiment
with small shield designs using various ferromagnetic and conductive materials,
read selected chapters in the EPRI Handbook, and call VitaTech
Engineering, LLC. (703-440-9400). Do not attempt any
large-scale room shield designs. Only experienced 60-Hz magnetic shielding
design companies have the technical expertise to design and successfully
install complex shielding systems for offices, work areas, and apartments. Table of Contents
REFERENCES
Feychting, M., and A. Ahlbom. 1992. "Magnetic Fields and
Cancer in People Residing near Swedish High Voltage Power Lines," IMM-rapport
6/92. Institute fvr miljomedicin, Korolinska institute, Stockholm,
Sweden.
Electric and Magnetic Fields Research and Public Dissemination
Program (EMF RAPID). 1995. Questions and Answers About EMF Electric
and Magnetic Fields Associated with the Use of Electric Power, pages
28-29. National Institute of Environmental He alth Sciences and U.S.
Department of Energy: GPO #DOE/EE-0040.
Lee, J., et al. 1993. "Electrical and Biological Effects
of Transmission Lines: A Review," Electric and Magnetic Fields, pages
13-23. U.S. Department of Energy Bonneville Power Administration.
Office of Radiation Programs. 1980. "Evaluation of Health
and Environmental Effects of Extra High Voltage (EHV) Transmission," Quantitative
Description of Voltages and Currents Induced in Objects by the Fields, pages
37-69. U.S. Environmental Pr otection Agency: # ORP/SEPD 80-13.
Johnson, T., et al. 1993. "Magnetic Field Reduction Research," Basic
Source Types, pages 4-7. Empire State Electric Energy Research
Corporation (ESEERCO): EP90-48.
Clairmont, B., et. al. 1994. "Handbook of Shielding Principles
for Power Systems Magnetic Fields- Volume 1," Basic Magnetic Field
Principles, pages 2-15 to 2-19, Introduction to Shielding Principles, pages
3-1 to 3-8. Electric Power Resea rch Institute (EPRI): EPRI TR-103630-V1
George, E., 1992. "MPR2: An Overview and Update," Ergonomics,
Inc. |